Residential stair code, section by section.

R311.7 stairways and R312 guards for one- and two-family dwellings and townhouses. Rows are measured the way an inspector measures them and note the UWP tread, rail or baluster that meets the line.

Reflects 2021 IRC. Adoption is local and amended — confirm the edition your authority having jurisdiction has adopted.

Riser
7¾″ max
Tread
10″ min, nose to nose
Handrail
34″–38″ above nosing line
Guard
36″ · 4″ sphere
How to read these tables

Three tables, one flight

Geometry first — the numbers that are fixed once the stringers are cut. Then handrails and guards, which are set by the railing system. Where a UWP part is dimensioned to a rule, the note says so; where a rule is about the stair as built, the note tells you what to check on site.

Stair geometry

Dimensions are measured the way the code measures them: risers tread-top to tread-top, treads nosing to nosing, headroom from the sloped nosing line.

  • Stair widthR311.7.1

    36″ minimum clear above the handrail height. Below the handrail: 31½″ clear with one rail, 27″ with rails both sides.

    Handrails may project up to 4½″ into the required width on each side.

  • HeadroomR311.7.2

    6′-8″ (80″) minimum, measured vertically from the sloped line of tread nosings.

  • Vertical rise per flightR311.7.3

    12′-7″ (151″) maximum between floor levels or landings.

  • Riser heightR311.7.5.1

    7¾″ maximum, tread top to tread top.

    Most residential stairs are built at 7″–7¾″. The UWP Stair Calculator checks this live.

  • Riser uniformityR311.7.5.1

    No more than 3/8″ between the largest and smallest riser in a flight.

    This is the rule that governs retro-fit treads — see the Retro-Fit Tread Guide.

  • Open risersR311.7.5.1

    Permitted, but where the flight rises more than 30″ the opening between treads must not pass a 4″ sphere.

  • Tread depthR311.7.5.2

    10″ minimum, measured horizontally nosing to nosing.

    UWP 8070 bullnose treads are 11½″ deep including a 1¼″ nosing.

  • Tread uniformityR311.7.5.2

    No more than 3/8″ between the deepest and shallowest tread in a flight.

  • Winder treadsR311.7.5.2.1

    10″ minimum at the walk line (12″ in from the narrow side) and 6″ minimum at any point within the clear width.

    Pie-shaped and winder treads are milled from your template or our on-site measure.

  • Nosing projectionR311.7.5.3

    ¾″ minimum to 1¼″ maximum where the tread depth is under 11″. Not required at 11″ or deeper. Variation ≤ 3/8″.

    Stocked tread nosings run 1″–1¼″; square-edge profiles rely on tread depth ≥ 11″.

  • Nosing profileR311.7.5.3

    Radius of curvature ≤ 9/16″; bevel ≤ ½″.

  • LandingsR311.7.6

    Required at the top and bottom of each stairway. Width not less than the stair; 36″ minimum in the direction of travel.

    Exception: a landing is not required at the top where a door does not swing over the stair.

  • Walking surfaceR311.7.7

    Treads and landings sloped no steeper than 1:48 (2%) in any direction.

    A landing built low to take flooring and left proud is a change in level, not a slope.

  • Spiral stairwaysR311.7.10.1

    26″ minimum clear width; 6¾″ minimum tread depth at a point 12″ from the narrow edge; risers 9½″ maximum; 6′-6″ headroom; all treads identical.

    Pie-shaped treads are milled to the fabricator’s template with the column notch.

  • IlluminationR303.7

    Interior stairways lit, with a light source that reaches every tread and landing at 1 foot-candle minimum.

Handrails

One handrail is required on any flight with four or more risers. Height is measured from the nosing line, not from the tread surface.

  • Where requiredR311.7.8

    At least one side of every flight with four or more risers.

  • HeightR311.7.8.1

    34″ minimum to 38″ maximum, measured vertically from the sloped line of tread nosings.

    Size baluster length so the rail top lands in the band — the UWP handrail pages list rail thickness.

  • Wall clearanceR311.7.8.3

    1½″ minimum between the wall and the handrail.

  • ProjectionR311.7.8.2

    Handrails may project no more than 4½″ into the required stair width at or below handrail height, on each side.

    The projection includes the bracket. A wide moulded rail on a stand-off bracket can exceed it on a 36″ stair.

  • ContinuityR311.7.8.4

    Continuous the full length of the flight, from a point above the top riser to a point above the lowest riser. Ends return to a wall or terminate at a newel post or safety terminal.

    Volutes, turnouts and starting easings are the code-recognized way to terminate at the bottom.

  • Type I grip — circularR311.7.8.5

    1¼″ minimum to 2″ maximum outside diameter.

  • Type I grip — non-circularR311.7.8.5

    Perimeter 4″ to 6¼″ with a maximum cross-section of 2¼″.

    Every UWP Original slab, bar and bullnose profile is dimensioned to clear Type I with margin.

  • Type II gripR311.7.8.5

    Perimeter over 6¼″ with a graspable finger recess on both sides: recess 5/16″ deep within 7/8″ below the widest point, and the rail above the recess 1¼″ to 2¾″ wide.

    The 6010 / 6210 / 6710 family and the wider UWP Originals qualify as Type II.

Guards

A guard is required wherever the open side of a walking surface is more than 30″ above the floor or grade within 36″ horizontally.

  • Where requiredR312.1.1

    Open sides of stairs, landings, balconies and porches more than 30″ above the floor or grade below, measured within 36″ horizontally.

  • Height — floors and landingsR312.1.2

    36″ minimum above the walking surface.

  • Height — open side of stairsR312.1.2

    34″ minimum, measured vertically from the nosing line.

    A guard rail at 34″–38″ can double as the stair handrail if it meets the grip rules.

  • OpeningsR312.1.3

    Must not pass a 4″ sphere.

    Baluster centers ≈ 4″ + one baluster width. The UWP baluster guides carry the spacing math.

  • Openings — stair triangleR312.1.3 exc. 1

    The triangle formed by tread, riser and guard bottom rail may not pass a 6″ sphere.

  • Openings — open side of stairsR312.1.3 exc. 2

    Guards on the open side of a stair may not pass a 4-3/8″ sphere.

Loads

Table R301.5 sets the live loads a stair and its railing system are designed for. The 200 lb concentrated load at the top of the guard is the one that decides how a newel is fastened.

  • Stair live loadTable R301.5

    40 psf uniformly distributed.

  • Tread concentrated loadTable R301.5, note

    300 lb on an area of 4 sq in, at any point on any tread, where it produces greater stress than the uniform load.

    Governs open-riser and cantilevered treads, where the tread spans free. Conventional stringer stairs are prescriptive.

  • Handrail and guard loadTable R301.5

    200 lb concentrated, applied in any direction at any point along the top of the handrail or guard.

    200 lb at the top of a 36″ post is 600 ft-lb at the base. Newels are through-bolted to framing or set with a rated mounting bolt into blocking.

  • Guard in-fill loadTable R301.5

    50 lb horizontal on a 1 sq ft area, including openings and the space between rails, not concurrent with the top-rail load.

    Balusters set into the tread and the rail, not surface-fixed.