Graspability by profile, and the guard rules around it.

The grip-size rule is the one a wood handrail most often fails on paper. Every UWP profile is listed below with its measured perimeter and type, read from the same geometry that cuts the knife.

Reflects 2021 IRC · 2021 IBC. Adoption is local and amended — confirm the edition your authority having jurisdiction has adopted.

Type I perimeter
4″–6¼″ · 2¼″ max section
Type II perimeter
Over 6¼″ with finger recess
Profiles listed
18 UWP handrails
The rule

Type I and Type II, explained

IRC R311.7.8.5 and IBC 1014.3 describe the same two shapes. A rail is compliant if it fits either one; the choice between them is a design decision, not a code one — unless the rail is on an accessible route, where §505 keeps the Type I dimensions.

Type I

Circular 1¼″–2″ outside diameter, or any other shape with a perimeter of 4″ to 6¼″ and a cross-section no larger than 2¼″.

The hand wraps the whole rail. Slab, bar and bullnose profiles up to about 2″ × 1⅜″ land here. Required wherever an accessible route calls for a rail the hand can close around.

Type II

Perimeter over 6¼″ with a graspable finger recess on both sides — the recess at least 5/16″ deep within 7/8″ below the widest point, and the rail above the recess 1¼″–2¾″ wide. Edges radiused at least 0.01″.

The fingers hook under a shoulder instead of wrapping the rail. The traditional 6010 / 6210 / 6710 family and the wider UWP Originals are Type II — the profile is shaped so the recess is part of the mould, not an afterthought.

Catalog

UWP handrail profiles by grip type

Perimeters are measured on the profile geometry the product pages, drawings and knives share. Each profile is dimensioned to clear its type with margin rather than sit on the minimum, so a reground knife still leaves a compliant rail.

Type I

Perimeter 4″–6¼″. Suitable for accessible routes.
ProfileFamilySectionPerimeterGrip
UW9601UWP Original Ploughed2" × 1⅛"5.267″Type I
UW9615UWP Original Profile1¾" × 1½"5.313″Type I
UW9602UWP Original Ploughed2" × 1⅜"5.451″Type I
UW9611UWP Original Profile2" × 1⅜"5.595″Type I
UW9606UWP Original Wall Rail1¼" × 2"5.606″Type I
UW6060UWP Original Profile2" × 1-1/32"5.848″Type I
UW9613UWP Original Profile1⅞" × 1½"5.925″Type I
UW9610UWP Original Profile1⅞" × 1½"6.018″Type I
UW9614UWP Original Profile1⅞" × 1½"6.029″Type I
UW9612UWP Original Profile2" × 1½"6.121″Type I

Type II

Perimeter over 6¼″ with the finger recess formed in the profile.
ProfileFamilySectionPerimeterGrip
UW9620UWP Original Profile2⅜" × 2"7.088″Type II
UW9617UWP Original Profile2½" × 2"7.259″Type II
UW9621UWP Original Profile2½" × 1¾"7.782″Type II
UW9603UWP Original Ploughed2" × 2½"8.746″Type II
UW9609UWP Original Profile2⅝" × 2¼"8.804″Type II
UW9608UWP Original Profile2⅜" × 2¼"9.999″Type II
UW9605UWP Original Ploughed2⅝" × 3¼"10.981″Type II
UW9604UWP Original Ploughed2½" × 3⅛"11.06″Type II

Profiles that predate the measured-perimeter program are listed on the handrail catalog with a section drawing; ask for the perimeter on any of them.

Handrails

One handrail is required on any flight with four or more risers. Height is measured from the nosing line, not from the tread surface.

  • Where requiredR311.7.8

    At least one side of every flight with four or more risers.

  • HeightR311.7.8.1

    34″ minimum to 38″ maximum, measured vertically from the sloped line of tread nosings.

    Size baluster length so the rail top lands in the band — the UWP handrail pages list rail thickness.

  • Wall clearanceR311.7.8.3

    1½″ minimum between the wall and the handrail.

  • ProjectionR311.7.8.2

    Handrails may project no more than 4½″ into the required stair width at or below handrail height, on each side.

    The projection includes the bracket. A wide moulded rail on a stand-off bracket can exceed it on a 36″ stair.

  • ContinuityR311.7.8.4

    Continuous the full length of the flight, from a point above the top riser to a point above the lowest riser. Ends return to a wall or terminate at a newel post or safety terminal.

    Volutes, turnouts and starting easings are the code-recognized way to terminate at the bottom.

  • Type I grip — circularR311.7.8.5

    1¼″ minimum to 2″ maximum outside diameter.

  • Type I grip — non-circularR311.7.8.5

    Perimeter 4″ to 6¼″ with a maximum cross-section of 2¼″.

    Every UWP Original slab, bar and bullnose profile is dimensioned to clear Type I with margin.

  • Type II gripR311.7.8.5

    Perimeter over 6¼″ with a graspable finger recess on both sides: recess 5/16″ deep within 7/8″ below the widest point, and the rail above the recess 1¼″ to 2¾″ wide.

    The 6010 / 6210 / 6710 family and the wider UWP Originals qualify as Type II.

Guards in practice

Baluster spacing math

The 4″-sphere rule sets the clear opening, not the centers. Maximum on-center spacing is 4″ plus one baluster width; set them slightly tighter to absorb layout drift, and lay out from the center of the run so the end gaps match.

BalusterMax on-center · field settingNote
½″ square iron4½″ nominal · set at 4-3/8″M-series iron. Three per tread on a 10″–11″ run — two leaves about a 4½″ gap and fails the 4″ sphere.
9/16″ square iron4-9/16″ nominal · set at 4-3/8″Heavier-gauge patterns.
1¼″ square wood (4500 / 5060)5¼″ nominal · set at 5″Plowed rail with 6006 fillet between.
1¾″ turned wood (5015 / 5160)5¾″ nominal · set at 5½″Measure at the narrowest turning, not the square block.

On the rake, the opening is measured perpendicular to the rail, so the same centers that pass on a level guard pass on the stair. The tread / riser / bottom-rail triangle at each step is the exception — it gets the 6″ sphere. The full layout method is in the iron and wood baluster installation guides.

Guards

A guard is required wherever the open side of a walking surface is more than 30″ above the floor or grade within 36″ horizontally.

  • Where requiredR312.1.1

    Open sides of stairs, landings, balconies and porches more than 30″ above the floor or grade below, measured within 36″ horizontally.

  • Height — floors and landingsR312.1.2

    36″ minimum above the walking surface.

  • Height — open side of stairsR312.1.2

    34″ minimum, measured vertically from the nosing line.

    A guard rail at 34″–38″ can double as the stair handrail if it meets the grip rules.

  • OpeningsR312.1.3

    Must not pass a 4″ sphere.

    Baluster centers ≈ 4″ + one baluster width. The UWP baluster guides carry the spacing math.

  • Openings — stair triangleR312.1.3 exc. 1

    The triangle formed by tread, riser and guard bottom rail may not pass a 6″ sphere.

  • Openings — open side of stairsR312.1.3 exc. 2

    Guards on the open side of a stair may not pass a 4-3/8″ sphere.

Guards

  • Where required1015.2

    Open sides of walking surfaces more than 30″ above the floor or grade below, within 36″ horizontally.

  • Height1015.3

    42″ minimum above the walking surface or nosing line.

    Exceptions: 36″ in R-3 and R-2 dwelling units; 34″–38″ where the top of the guard is the stair handrail.

  • Openings below 36″1015.4

    Must not pass a 4″ sphere.

  • Openings 36″ to 42″1015.4 exc. 1

    Must not pass a 4-3/8″ sphere.

  • Stair triangle1015.4 exc. 2

    The tread / riser / bottom-rail triangle may not pass a 6″ sphere.